Industrial 4-20mA online zirconia oxygen analyzer for combustion control Boiler Furnace
Brand Yongan Electronics
Product origin Wuxi, Jiangsu Province
Delivery time 1-10piece(5-7 days) ;20~100piece(10-15 days)
Supply capacity Annual Production Volume 10,000+
Product Highlights:
1.The zirconia oxygen probe supports two specifications—low-temperature (<700℃) and high-temperature (700–1100℃)—with the wide-temperature model adaptable to a diverse range of operating conditions.
2.The zirconia oxygen transmitter provides a 4–20 mA output signal, enabling direct networking and interfacing with computers and DCS systems.
3.The flue gas oxygen analyzer features a high-definition LED digital display that provides clear and intuitive readings, facilitates on-site calibration, and ensures measurement accuracy.
Product details:
The ZOY Series Intelligent Zirconia Oxygen Analyzers enable rapid, accurate, and online monitoring and analysis of the flue gas content generated during the combustion process in equipment such as boilers, kilns, and heating furnaces. This facilitates low-oxygen combustion control, thereby achieving energy conservation objectives and reducing environmental pollution.
Product Specification Sheet:
Model Number | ZOY series |
Prodect Name | Zirconia Oxygen Analyzer |
Detection Range | 0-10%vol,0-20%vol,0-25%vol |
Power Supply | 220VAC ±10% 50Hz/60Hz |
Language Support | English |
Qutput Signal | 4-20mA or RS485 |
Display | LED display |
Flue gas temperature | ≤0-700℃ |
Ambient Temperature | 0–50°C |
Relative Humidity | <90% RH (non-condensing) |
Insertion Depth | 200mm~1500mm (Customizable) |
Flue Gas Pressure | -10 kPa to +10 kPa |
Power Consumption | ≤ 100 W |
Response Time | Reaches 90% within 5 seconds upon introduction of standard gas. |
Model Number | ZOY series |
Prodect Name | Zirconia Oxygen Analyzer |
Detection Range | 0-20%vol,0-25%vol |
Power Supply | 220VAC ±10% 50Hz |
Language Support | English |
Qutput Signal | 4-20mA or RS485 |
Display | LED display |
Flue gas temperature | ZOY-4:0-700℃ ZOY-5:700~1100℃ |
Ambient Temperature | 0–50°C |
Relative Humidity | <90% RH (non-condensing) |
Insertion Depth | 200mm~1500mm (Customizable) |
Product advantages:
1.Comprehensive Certifications: ISO 9001, ISO14001, and ISO45001 ,ensuring full compliance and qualification.
2. Professional Technical Support:Our technical engineers work directly with clients to assist in determining the proper insertion depth for zirconia probes and selecting the appropriate model based on flue gas temperature, as well as to address any product-related concerns clients may have both before and after placing an order.
3. Rapid After-Sales Response: In the event of a quality issue, our technical engineers will immediately diagnose the root cause of the fault and promptly arrange for a replacement shipment or provide a corrective solution.
4. Brand Customization: We offer customization services, including the integration of your company logo and name.
Enterprise Advantages
Company Introduction:

Wuxi Yong'an Electronic Technology Co.,Ltd with 15 years of experience in the industr, it has 4 modern production lines and isequipped with more than 10 professional intelligent production and testing instruments, including precision pressure testing machines,airtightness testers, highand low temperature aging test chambers, Bas precision calibrators,etc, covering the entire process of produc-tion, assembly, calibration, and quality inspection.
With excellent product quality and standardized management system, we have obtained multiple authoritative certifications, including ISO9001 certification, ISO14001 certification, and IS045001 certufication. A thesame time, we have muliple authoritative product qualifications such as CPA, CCEP, CE, SIL, ATEX, explosion-proof certificates. Ourproduct quality, safety, and stability meet the industry's high standard specifications.
Certificate:

FAQ;
Q1:In which industrial scenarios are zirconia oxygen analyzers primarily applicable?
In-situ Zirconia Oxygen Analyzer Widely applied in scenarios requiring the monitoring of oxygen content in flue gas or process gas, including:
a.Online zirconia oxygen analyzers for monitoring oxygen levels in boiler flue gas at thermal power plants
b.Zirconia oxygen analyzers with 4–20 mA outputs for combustion optimization in petrochemical cracking furnaces and heating furnaces
c.Zirconia oxygen detectors for cement rotary kilns, glass melting furnaces, and metallurgical heating furnaces
d.Industrial zirconia oxygen sensors for waste incinerators and hazardous waste treatment facilities
Zirconia oxygen meters for industrial boilers, hot blast furnaces, and thermal fluid heaters
Q2:What is the operating temperature range of a zirconia probe?
The probe of the industrial zirconia oxygen sensor features an integrated heating element that heats the zirconia component to a constant operating temperature of 700℃.
Q3:When installing zirconia oxygen analyzer, how are the probe insertion depth and installation angle determined?
A.Insertion Depth: Ensure that the zirconia sensing element at the tip of the probe is positioned within the central airflow zone of the pipeline; typically, the insertion depth should be between 1/3 and 1/2 of the pipe's diameter.
B.Installation Angle: We recommend installing the probe horizontally with a slight downward tilt of 3–5°, installing it vertically downward, to prevent condensate from flowing back into the interior of the probe.
C.Flange Specifications: We provide standard DN50 flanges and also support custom non-standard specifications.